Key specifications
| Capacity | 4,073 kWh, 2,037 kW (0.5P) |
|---|---|
| Cell | LFP 306 Ah, 5P2P416S |
| Voltage | 1,331.2 VDC rated, 1,040–1,500 VDC |
| Dimensions | 6,058 × 2,438 × 2,896 mm, ~36 t |
| Cooling | liquid cooling |
| Protection | IP55 battery/electrical room, C4 (C5 optional) |
| Operating temp | -25…+55 °C |
| Certifications | UL1973, UL9540, UL9540A, IEC62619, IEC62477, IEC62933-5-2, NFPA855 |
| Communication | CAN, Modbus/TCP |
Manufacturer data; details, options and current revision in the official datasheet. Subject to change.
Typical applications
- Utility-scale and large C&I storage
- PV co-location
- peak shaving
- grid services
Why from BST.SOLAR?
- Design and sizing for your load profile – not a catalogue sale.
- Installation, grid connection and ComAp-based control from one team.
- Commissioning, remote monitoring and O&M support in Hungary.
Application in practice
The CATL EnerC Plus is the mature 20 ft liquid-cooled LFP container that many Hungarian and CEE projects are built on: 4,073 kWh and 2,037 kW at 0.5P from 306 Ah cells in a 5P2P416S arrangement. Typical uses are HUPX arbitrage and aFRR blocks of several MW behind an MV connection, storage co-located with PV plants and large industrial sites with their own transformer station. The container is DC-only, so it is paired with external PCS blocks, an MV transformer and a plant EMS communicating over CAN and Modbus/TCP.
BST designs the block around the 1,331.2 V rated voltage and the 1,040–1,500 V window of the chosen PCS, prepares the foundation for the roughly 36 t, 6,058 × 2,438 × 2,896 mm unit, and handles the grid connection and EMS/SCADA integration. IP55 and C4/C5 corrosion protection with −25 to +55 °C operation allow outdoor installation. The UL 1973/9540/9540A, IEC 62619/62477/62933-5-2 and NFPA 855 certificates support permitting, and wide availability through EU distributors shortens lead times. We commission the plant and provide service.
When to choose this product
- You need a proven 4 MWh-class DC container at 0.5P with short lead times from EU distributors.
- Your PCS operates in the 1,040–1,500 V DC window and communicates over CAN or Modbus/TCP.
- Outdoor installation with IP55 and C4/C5 corrosion class in a −25 to +55 °C climate is required.
- Comprehensive UL and IEC certification is needed for the Hungarian permitting and insurance process.
Frequently asked questions
Which PCS can be used with the EnerC Plus?
Any 1,500 V-class PCS whose DC window covers 1,040–1,500 V and which supports CAN or Modbus/TCP communication with the container BMS. For 2,037 kW per container BST typically pairs a matching central PCS and MV transformer and verifies the protection coordination between PCS, container and the connection point.
How does the EnerC Plus compare with the TENER S?
EnerC Plus offers 4,073 kWh and 2,037 kW in the 20 ft format, while the newer TENER S reaches 6.017 MWh in the same footprint with lower auxiliary consumption. EnerC Plus remains attractive where availability, cost per block and a long track record matter. BST quotes both for comparison.
What are the site requirements for an EnerC Plus container?
A level foundation rated for about 36 t, service clearances around the 6,058 × 2,438 × 2,896 mm unit, cable routes to the PCS and MV transformer, and a fire protection concept supported by its UL 9540A and NFPA 855 documentation. BST provides the layout, permitting documents and commissioning.
Need this equipment for your project?
Send us your load profile or project outline and we return a sized proposal with delivery time.
Call our engineering team: +36 1 451 8070