Skip to Content

Equipment › ComAp

ComApControl / EMS

ComAp InteliGen 500 G2 paralleling controller with 5" display

Paralleling genset controller with built-in 5" colour display for single and multiple gensets in grid-tied or island operation, incl. hybrid PV support.

Second-generation InteliGen 500 with a built-in 5" display: single or multiple gensets, grid-tied or island, with PV control for hybrid sites. Multi-ECU support for Stage V / Tier 4 Final engines, IP65 front and plug-in LAN/4G modules for remote access.

Request a quotationManufacturer datasheet (PDF)

ComAp InteliGen 500 G2 paralleling controller with 5" display

Key specifications

ApplicationsSingle/multiple gensets, grid-tied or island, hybrid microgrid with PV control
Display5" colour built-in
CommunicationModbus RTU/TCP, SNMP v1/v2c/v3, J1939, CAN, RS232/RS485, USB, LAN/4G via plug-in modules, AirGate 2.0
Controller cooperationup to 32 gen-set/mains/tie controllers
EnginesMulti-ECU support, Stage V / Tier 4 Final
ProtectionIP65 front, IP20 rear
Operating temp-20…+70 °C
Dimensions227×157×48 mm
StandardsEN 61000-6-2/4, EN 61010-1, EN IEC 60255, UL 6200
SecurityISA 62443 L2-3

Manufacturer data; details, options and current revision in the official datasheet. Subject to change.

Typical applications

  • Diesel genset paralleling
  • standby and prime power plants
  • rental
  • hybrid genset + PV sites

Why from BST.SOLAR?

  • Design and sizing for your load profile – not a catalogue sale.
  • Installation, grid connection and ComAp-based control from one team.
  • Commissioning, remote monitoring and O&M support in Hungary.

Application in practice

The InteliGen 500 G2 covers the most common genset applications we see in Hungary: a single standby genset with automatic mains failure, two to several gensets in parallel on an industrial site or farm, and island or grid-tied operation with hybrid PV support where the controller curtails or coordinates PV inverters while the gensets carry the load. It talks J1939 to modern Stage V / Tier 4 Final engines, communicates with the site EMS over Modbus RTU/TCP and SNMP, and can be paralleled with up to 32 controllers over CAN.

BST supplies the controller programmed for the specific engine and switchgear, including multi-ECU support, and integrates it with the PCS and BMS when storage is added later. Communication uses RS232/RS485, USB and LAN/4G plug-in modules with AirGate 2.0 for secure remote access and WebSupervisor monitoring. The 227 × 157 × 48 mm unit mounts in the cabinet door with an IP65 front, suitable for genset canopies and outdoor enclosures; check the -20 to +70 °C rating for unheated winter sites. ISA 62443 and UL 6200 compliance are built in.

When to choose this product

  • Single or multiple gensets, grid-tied or island, where a built-in 5-inch colour display replaces a separate HMI.
  • Modern Stage V / Tier 4 Final engines with J1939 and multi-ECU communication are to be controlled.
  • Hybrid PV support is needed so that gensets and PV inverters coexist in island operation.
  • Door mounting with an IP65 front in a genset canopy or outdoor enclosure, with up to 32 controllers on CAN.

Frequently asked questions

?

Does the InteliGen 500 G2 support PV inverters running together with gensets?

Yes. The InteliGen 500 G2 includes hybrid PV support: in island operation it keeps the gensets within a safe load window while PV contributes, and curtails PV when needed to maintain stability. For full energy storage control with a PCS and BMS, an InteliNeo controller is added. BST designs the control hierarchy for the site.

?

What is the difference between the InteliGen 500 G2 and the InteliGen 1000?

The InteliGen 500 G2 has a built-in 5-inch display, IP65 front, up to 32 controllers and a -20 to +70 °C rating, targeting standard single- and multi-genset sites. The InteliGen 1000 offers 3× Ethernet, SNMP, up to 64 controllers, hot-swap and CAN redundancy and uses a separate InteliVision display for complex, critical plants.

?

Can the InteliGen 500 G2 be monitored remotely in Hungary?

Yes. With the LAN or 4G plug-in module and AirGate 2.0, the controller is reachable through WebSupervisor without a fixed IP address, giving alarms, event history and parameter access from anywhere. Modbus TCP and SNMP also allow integration into a customer SCADA. BST configures remote access during commissioning and offers service contracts.

Need this equipment for your project?

Send us your load profile or project outline and we return a sized proposal with delivery time.

Request a quotation

Call our engineering team: +36 1 451 8070